ICA UPS SE1603C33 Capacity 160000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Model : UPS SE1603C33
Capacity : 160000 VA / 160000 W
INPUT  
Nominal Voltage : 380 / 400 / 415 Vac (3Ph+N+PE)
Operating Voltage Range : 138 ~ 485 Vac
Operating Frequency Range : 40Hz ~ 70Hz (50/60Hz Auto-Sensing)
Power Factor : ≥0.99
Bypass Voltage Range : 220Vac Max. voltage: +25% (optional +10%, +15%, +20%)
230Vac Max. voltage: +20% (optional +10%, +15%)
240Vac Max. voltage: +15% (optional +10%)
Min. voltage: -45% (optional -10%, -15%, -20%, -30%)
Bypass Frequemcy Range : Frequency synchronize tracing range: ±10%
ECO Range : Same as bypass
Harmonic Distortion (THD) : ≤3%
BATTERY    
Battery Voltage : ±240Vdc
Backup time : 6 ~ 10 minutes depending on load
Charge Current (A) (Charger current can be set according to battery capacity installed : Max. current 60A
Battery configuration : External
OUTPUT    
Output Voltage : 380 / 400 / 415 Vac (3Ph+N+PE)
Power Factor : 1.0
Voltage Regulation : ±1%
Frequency Line Mode : ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency (optional)
Frequency Bat. Mode : 50/60 (±0.2%)Hz
Crest Factor : 3:1
Harmonic Distortion (THD) : ≤2% with linear load
≤4% with non-linear load
Efficiency : 95.5%
SYSTEM FEATURES    
Transfer Time : Utility to Battery: 0ms; Utility to Bypass: 0ms
Protection : Short circuit, Overload, Over temperature, Battery low, Fan fault alarm
Overload : Load ≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150%: 1.2s shutdown inverter
Short Circuit : Hold Whole System
Alarm : Overload, Utility abnormal, UPS fault, Battery low, etc
Communication : USB, RS232, RS485, Parallel port, REPO port, LBS port, dry contact, Intelligent slot, SNMP card (optional), Relay card (optional)
Backfeed protection : Support
Remote LCD : Support
ENVIRONMENTAL    
Operating Temperature : 0 ~ 40ºC
Storage Temperature : -25 ~ 55ºC (No battery)
Humidity Range : 0 ~ 95% (Non-condensing)
Altitude : <1500m, When >1500m, lower the rated power for use
Noise Level : <66dB
PHYSICAL UPS Without External Battery (UPS Only)
Dimension D x W x H (mm) : 850 x 442 x 1200
Net Weight : 200
Gross Weight : 218
STANDARDS    
Safety : IEC/EN62040-1, IEC/EN60950-1, IEC/EN62477-1
EMC :

IEC/EN62040-3, IEC62040-2, IEC61000-2-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11