M200 FA33

ICA UPS M200 FA33 Capacity 200 Kva, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Type : UPS Frame M200FA33
Capacity : 10 – 200 K / 9 – 180K
INPUT
Nominal voltage : 380 / 400 / 415 Vac (3Ph+N+PE)
Operating voltage range : 208 – 478 Vac
Operating frequency range : 40 – 70 Hz
Power Factor : ≥0.99
Bypass Voltage Range : Max. Voltage : 220V + 25% (optional +10%, +15%, +20%) 230V 20% (optional +10%, +15%) 240V 15% (optional +10%), Min. Voltage : -45% (optional -20%, -30%), Frequency protection range : ±10%
Harmonic distortion (THDi) : 2% (100% non-linear load)
General Input : Support
OUTPUT
Output voltage : 380 / 400 / 415 Vac (3Ph+N+PE)
Voltage regulation : ± 1%
Power factor : 0.9 / 1 (customized)
Output frequency : 1. Line Mode : ±1%, ±2%, ±4% ,±5%, ±10% of the rated frequency (optional)
2. Battery Mode : (50 / 60 ±0.1%) Hz
Crest factor : 3 : 1
Harmonic distortion (THDv) : ≤2% with linear load, ≤5% with non linear load
Efficiency : 95.5%
BATTERY 
Battery voltage : ±192 / ±204 / ±216 / ±228 /240 Vdc: battery quantity (optional)
Charge current : 60 A (Max.)
Backup time : Depends on the capacity of external batteries
SYSTEM FEATURES
Transfer time : Utility to Battery: 0ms: Utility to Bypass : 0ms
Overload Line mode : Load ≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately
Overload Bat. mode : Load ≤110&: last 10min, ≤125%: last 1min, ≤150%: last 1 s, ≥150% shut down UPS immediately
Overload Bypass mode : Breaker (10 Kva : 20 A / 15 Kva : 32 A / 20 Kva : 40 A)
Short circuit : Hold whole system
Nose suppression : Complies with EN62040-2
Communication interface : RS232, RS485, Dry Contact, Intelligent slot x 2 (SNMP card, Relay card optional)
ENVIRONTMENTAL
Operating temperature : 0 – 40ºC
Storage temperature : -25 ~ 55 ºC
Humidity range : 0 ~ 95% (non condensing)
Altitude : <1500m
Noise level : <65dB
PHYSICAL
IDimension (DxWxH) : 1100 x 600 x 2000 mm
Weight : 290 Kg
STANDARDS
Safety : IEC/EN62040-1, IEC/EN60950-1
EMC : IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8