RN 1102 C11

Type : UPS RN1102C11
Capacity : 10.000 VA / 9000 W
INPUT
Input mode : Single phase + Ground
Power factor : ≥0.99
Rating voltage : 220 / 230 / 240 Vac (can be set)
Rating frequency : 50 / 60Hz (auto sensing)
Voltage range : 120 ~ 276 Vac
Frequency range : 45 ~ 55Hz / 54 ~ 66Hz
Bypass voltage range : 220Vac max : 10%, 15%, 20% or 25%, default : 25% ; 230Vac max : 10%, 15% or 20%, default +20% ;240Vac max : +10% or 15%, default +15%
Min : 20%, 30% or 45%, default 45%
Bypass frequency range : ±1%, ±2%, ±4%, ±5%, ±10%
THDI : ≤3% (100% liner load, input THDV ≤1%) ; ≤5% (100% liner load, input THDV ≤1%)
BATTERY
Battery number : 16 / 18 / 20 pcs (can be set)
Battery type : VRLA
Charge model : Boost charge or float charge auto switch
Charge time : Boost charge up to 20Hr (Max)
Charge current (A) : 1A (S) / 10A (H)
OUTPUT
Output Type : Single phase + Ground
Ouput precision : 1.0%
Voltage distortion (THD) : ≤2% at 100% liner load; ≤5% at 100% non-liner load
Rating voltage : 220 / 230 / 240V
Frequency precision : ±0.1%
Rating frequency : 50 / 60Hz
Frequency track speed : 1 Hz/s
Overload : 105% ~ 110%, 1 Hr; 110% ~ 125%, 10min; 125% ~ 150%, 1min; ≥150% 200ms
Peak Value factor : 3 : 1
Efficiency at normal : ≥90%
Dynamic respond : 5.0%; 20ms
DC heft : ≤500mV
SWITCH
Between normal mode and battery mode : 0ms
Between Inverter mode and Bypass : 0ms ; Unlock : <15ms (50Hz), <13.33ms (60Hz)
Norse : <55dB (1m)
Display : LCD + LED
Safety : Metting IEC62040-1 GB4943
Max input voltage : 320Vac, 1 Hr
EMI : Conduction : IEC 62040-2; Radiation : IEC 62040-2; Harmonics : IEC 62040-2
EMS : IEC 62040-2
MTBF : 250.000Hr 1 + 1 400.000Hr
MTTR : 30min
Isolation resistance : >2M Ω (500Vdc)
Isolation intension : 2820Vdc, <3.5mA, 1 min
Surge : Meeting IEC60664-1 1.2/50uS + 8/20uS 6Kv/3kA
Protection : Ip20
Parallel circuimfluence : 1 + 1 ≤ 8%, N + 1 ≤ 3%
Parallel equal current : 1 + 1 ≤ 8%, N + 1 ≤ 10%
Dimension (DxWxH) : 790 x 580 x 290 mm
Weight : 30 Kg