SIN 10 KEP

ICA UPS SIN 10 KEP Capacity 10.000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Model : UPS SIN10KEP
Capacity : 10000 VA
Power Rating : 9000 W
INPUT
Operating voltage range : 380/400/415Vac (380-25%, 415+20%), (3Ph+N+PE)
Operating frequency range : 50 / 60Hz ± 5Hz
Power factor : >0.97 (with filter)
Rated current : 15 A
OUTPUT
Output voltage : 380/400/415Vac (±1%)
Output frequency : 50 / 60Hz (±0.05%)
Frequency regulation (battery mode) : 50 / 60Hz ± 0.05%
Output waveform : Sine wave
Power factor : 0.9 (lagging)
Harmonic distortion (THD) : <3% (linear load)
Overload capacity : When 110% / 125% / 150% overload, maintain 60min/ 10min/ 1min
Crest factor : 3 : 1 (max)
Efficiency : >89%
BYPASS
Rated voltage : 380/400/415Vac
Bypass voltage range : Upper limit: +10%, +15%, +20% can be set ; LOwer limit: -10%, -20%, -30%, -40% can be set
Rated frequency : 50 / 60Hz
Bypass frequency range : ±2% (±10%, ±20% can be set)
Transfer time to bypass : 0 ms / 1 ms
Overload capacity : 15 times the rated current (10ms), 5 times the rated current (5s)
BATTERY
Battery voltage : 384 Vdc
Backup time (min) External battery : 10
SYSTEM FEATURES
Transfer time : 0ms (Line mode – Battery mode)
Overload : 110% / 60min, 125% / 10min, 150% / 1min
Communication interface : LCD display, LED indication, Dry contact, RS232, RS485, SNMP card (optional)
Optional : Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor, Bypass current sharing inductor
PANEL DISPLAY
LED : Indicate the status of input, inverter, bypass, battery, output
LCD : Display input/output voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record, set parameters
ENVIRONMENTAL
Operating temperature : 0 ~ 40ºC
Storage temperature : -25ºC ~ 55ºC
HUmidity range : 0 ~ 95% (non-condensing)
Altitude : <1500m
Noise level : <60 dB
PHYSICAL
Weight Netto : 217 Kg
Weight Gross : 272 Kg
Dimension (WxDxH) : 570 x 800 x 1195 mm
STANDARDS
Safety : IEC/EN62040-1 IEC/EN60950-1
EMC : IEC/EN62040-2; IEC61000-4-2; IEC61000-4-3; IEC601000-4-4; IEC61000-4-5; IEC61000-4-6; IEC61000-4-8