SIN 100 KEP

ICA UPS SIN 100 KEP Capacity 100.000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Type : UPS SIN100KEP
Capacity : 100.000 VA / 90.000 W
Rentang tegangan : 380 / 400 / 415 Vac (-25% ~ +20%) 3 fase, 5 kawat
Rentang rekuensi : 50 / 60 Hz ±5 Hz identifikasi otomatis
Faktor daya : >0.8 (tanpa filter), >0.9 (dengan filter)
Nilai arus : 186A
OUTPUT
Rentang tegangan : 380 / 400 / 415 Vac ±1%
Frekuensi : 50 / 60Hz
Stabilitas frekuensi : 50 / 60 (±0.05%) Hz pada mode baterai
Bentuk gelombang : Gelombang sinus
Faktor daya : 0.9 (lag)
Distorsi harmonik total : <3% (beban linier) / <5% (bukan beban linier)
Kapasitas beban lebih : 110% / 125% / 150% untuk 60 menit / 10 menit / 1 menit
Faktor puncak : 3 : 1 (Max.)
Efisiensi : 91%
Waktu perpindahan : 0 ms; mode normal ke mode baterai atau sebaliknya
BYPASS
Rentang tegangan : 380 / 400 / 415 Vac (3 fase 5 kawat)
Rentang proteksi tegangan : -40% ~ +20%
Rentang frekuensi : 50 / 60Hz
Rentang proteksi frekuensi : ±20%
Waktu perpindahan : 0 ms / 2 ms
Kapasitas beban-lebih (In) : 15In, 10 ms
BATERAI
Tegangan : 384 Vdc
PANEL
LED : Input, Inverter, Bypass, Battery dan Output
LCD : Input voltage, Output voltage, Frequency, Power factor, Battery voltage, Battery current & status, Load percentages, UPS status, history record, Setting
Komunikasi Antarmuka : Dry contact, RS232, RS485, SNMP card slot
LINGKUNGAN KERJA
Kelembaban relatif : 0 ~ 95% (tanpa kondensasi)
Ketinggian : ≤1000mdpl, pengurangan 2% kapasitas setiap 100m, mulai dari 1000m sampai 2000m
Kebisingan : ≤70dB
Opsional : Filter harmonik, Adapter SNMP, Inductor current-sharing bypass
Dimensi (PxLxT) : 1160 x 805 x 1600mm