SIN 203C11
ICA UPS SIN 203C11 Capacity 20000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.
Model | : | UPS SIN203C11 |
Capacity | : | 20000 VA / 16000 W |
AC Input Voltage | : | Single Phase, 220 V |
AC Input Frequency | : | 50 ± 5% Hz |
AC Input Protection | : | MCB |
DC Input Voltage | : | 192 V |
DC Input Battery | : | 16 x 12 V, 24 Ah (External) |
DC Input Protection | : | MCB |
Charger Topology | : | SWITCHING REGULATION |
Charger Floating Voltage | : | 217.6 V |
Inverter Output Waveform | : | Pure Sinewave |
Inverter Output Distortion | : | <3% THD |
Inverter Output Topology | : | PULSE WIDTH MODULATION (PWM) |
Inverter Output Voltage | : | 220 ± 2% V |
Inverter Output Frequency | : | 50 ± 1 % Hz |
Inverter Output Efficiency | : | ± 86 % |
Transfer Time When AC Input Loss | : | 0 ms |
Static Transfer Switch | : | 2 ms From Inverter To Bypass; 0 ms Back To Inverter |
Back Up Time | : | 10 min |
Buzzer AC Input Abnormal | : | Intermittent Sound With 2 Seconds Interval |
Buzzer Battery Low | : | Intermittent Sound With 0.5 Second Interval |
Operation Temperature | : | 0 – 40°C |
Dimension (DxWxH) | : | 630 x 310 x 870 mm |
Weight Netto | : | 104 Kg |
Weight Gross | : | 114 Kg |
External Battery Type | : | UB1624 |
External Battery Dimension | : | 525 x 425 x 870 mm |
External Battery Weight | : | 168 Kg |