SIN 7501 C3

ICA UPS SIN 7501C3 Capacity 10000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Model : UPS SIN7501C3
Capacity : 10000 VA / 6500 W
AC Input Voltage : Three Phase, 4 Wire 380V
AC Input Frequency : 50 ± 5% Hz
AC Input Protection : No Fuse Breaker
DC Input Voltage : 192 V
DC Input Internal Battery : 16 x 12 V, 17 Ah
DC Input Protection : No Fuse Breaker
Charger Topology : SWITCHING REGULATION
Charger Floating Voltage : 216 V
Inverter Output Waveform : SINUSOIDA
Inverter Output Distorsion : < 3 % THD
Inverter Output Topology : PULSE WIDTH MODULATION (PWM)
Inverter Output Voltage : 220 ± 2% V
Inverter Output Frequency : 50 ± 1 % Hz
Inverter Output Efficiency : ± 85 %
Transfer Time When AC Input Loss : 0 ms
Static Transfer Switch : 2 ms From Inverter To By-Pass, 0 ms Back To Inverter
Back Up Time : 10 min
Buzzer UPS in Bypass Condition : Intermittent Sound With 30 Second Interval
Buzzer AC Input Abnormal : Intermittent Sound With 4 Second Interval
Buzzer Battery Low : Intermittent Sound With 1 Second Interval
Operation Temperature : 0 – 40°C
Dimension(DxWxH) : 765x 595 x 1120 mm
Weight Netto : 320 Kg
Weight Gross : 352 Kg